Case study Gardermoen Treatment Plant, Norway

Plant for nitrogen removal using de-icing fluid as an external carbon source.

  • Operational since: 1998.

Design data

Parameter Value
Total BOD7 2 680 kg/d
Total COD 5 480 kg/d
TN 704 kg/d
TP 101 kg/d
TSS 3 290 kg/d
Design flow 920 m³/h
Maximum flow 1 300 m³/h
PE 50 000
Temperature range 5-14°C

Effluent requirements

Parameter Årsmedel Maximalt värde
Phosphorous <0,25 mg TP/l and 95% reduction 1.5 mg/l
Nitrogen 70% reduction -
BOD7 <10 mg/l and 70% reduction 20 mg/l

Results

Parameter Influent Effluent Reduction
BOD7 180 (mg/l) 3 (mg/l) 98.3 (%)
TP 7.06 (mg/l) 0.17 (mg/l) 97.6 (%)
TN 45.05 (mg/l) 7.76 (mg/l) 82.8 (%)
NH4-N 30.89 (mg/l) 0.55 (mg/l) 98.2 (%)
Temperature (°C) 3.8-14°C    

Excellent plant performance since start-up. Total removal in 2001 was more than 80% on annual average.